MGE Galaxy 7000 GFC Shore Connect 500KvA

MGE Galaxy 7000 GFC Shore Connect 500KvA Front Left
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Left
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Left
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Right
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Straight
MGE Galaxy 7000 GFC Shore Connect 500KvA Back
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Left
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Right
MGE Galaxy 7000 GFC Shore Connect 500KvA Front Straight
MGE Galaxy 7000 GFC Shore Connect 500KvA Back
  • Performance 3 phase power protection specially designed for shore connection application, max capability up to 10 products in parallel.

  • Includes: Installation guide, Service manual

View Product Overview

G7TQ500CS Features

Key Features

Run time for load
Min-max
W
Run time for load
Enter the total load (power draw) of all devices to be protected by the UPS here. Based on the value entered we will estimate the run time that you will have during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.

The total load (power draw) entered exceeds the maximum value for this product (450000 W)

Please enter load to see estimated run time

The total load (power draw) entered is less than the minimum value for this product ({} W)

Max. Capacity Used
Max. Capacity Used
The maximum percentage of UPS capacity used to support your specified load.

Please enter load to see calculated "Max. Capacity Used"

Output power capacity
450.0kWatts / 500.0kVA
Nominal Output Voltage
400V 3PH, 415V 3PH
Nominal Input Voltage
415V 3PH, 480V 3PH
Input Connections
Hard wire 5-wire (3P + N + E)
Maximum Input Current
735.0A
MGE Galaxy 7000 GFC Shore Connect 500KvA
Performance 3 phase power protection specially designed for shore connection application, max capability up to 10 products in parallel.
Includes: Installation guide, Service manual
  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
  • Auto recognition of external batteries
    UPS recognizes when external battery packs are attached and automatically adjusts runtime.
  • Automatic internal bypass
    Pure static bypass switch without bridging contactor securing a fast and reliable transfer to and from bypass, rated for 125% nominal load.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Double conversion on-line topology
    Guarantees a consistently high level of power quality. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.
  • Dual mains input
    Increases availability by allowing the UPS to be connected to two separate power sources.
  • Manual maintenance bypass
    Reduces installation costs by eliminating the need for an external mechanical bypass.

Galaxy 7000 Features & Benefits

Manageability

Network management capability
Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet.

Availability

High availability architecture
Different running modes : hot stand-by, integrated parallel, or centralized static switch for multi-modules leading to availability architectures

Economy

Advanced electrical features
Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection.
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.

Compatiblity

Parallel capability
Multiple units can be placed in parallel to meet power capacity and redundancy requirements
Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability.
Output synchronization to external source
UPS systems can be synchronized with any other independent source for use with downstream static transfer switches.

Sustainability

EU CoC for UPS
Ensures that UPSs sold in the EU are highly efficient

Product Distribution

United Arab Emirates, Argentina, Austria, Australia, Belgium, Bulgaria, Brazil, Canada, Switzerland, Chile, China, Colombia, Costa Rica, Serbia and Montenegro, Czechia, Germany, Denmark, Algeria, Estonia, Egypt, Spain, Finland, France, Greece, Hong Kong SAR China, Croatia, Hungary, Indonesia, Israel, India, Italy, South Korea, Kazakhstan, Lithuania, Latvia, Morocco, Malaysia, Nigeria, Netherlands, Norway, New Zealand, Peru, Philippines, Poland, Portugal, Romania, Saudi Arabia, Sweden, Singapore, Slovenia, Slovakia, Thailand, Turkey, Taiwan, Ukraine, Vietnam, South Africa

Technical Specifications

Output

Max Configurable Power (Watts)
450.0kWatts / 500.0kVA
Neutral Output Current
938A
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Output Voltage Distortion
Less than 2 %
Output Frequency (sync to mains)
50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50 Hz Sync to mains, 60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised
Other Output Voltages
440 V
Load Crest Factor
2.5 : 1
Waveform type
Sine wave
Maximum Output Current
2369
Output Voltage THD
< 2% linear load and < 3% non-linear load
Bypass
Built-in maintenance bypass

Input

Input frequency
45 - 65 Hz
Input voltage range for main operations
340 - 460 (400 V)V
Input Total Harmonic Distortion
Less than 3 % for full load
Type of Input Protection Required
3-pole circuit breaker
Other Input Voltages
450 V
Maximum Short Circuit Withstand (Icw)
200.0kAmps
Input Power Factor at Full Load
1.0

Batteries & Runtime

Communications & Management

Control panel
Multifunction LCD status and control console
Emergency Power Off (EPO)
Yes
Available SmartSlot™ Interface Quantity
2

Physical

Maximum Height
1900MM, 190.0CM
Maximum Width
1812MM, 181.2CM
Maximum Depth
855MM, 85.5CM
Net Weight
1470.0KG
Shipping weight
1490.0KG
Shipping Height
2030MM, 203.0CM
Shipping Width
960MM, 96.0CM
Shipping Depth
1920MM, 192.0CM

Environmental

Operating Temperature
0 - 35 °C
Operating Relative Humidity
20 - 80 %
Operating Elevation
0 - 1015.9meters
Storage Temperature
-25 - 40 °C
Storage Relative Humidity
20 - 80 %
Storage Elevation
0 - 9144meters
Audible noise at 1 meter from surface of unit
72.0dBA
Protection Class
IP20

Conformance

Approvals
CE, EN 60950, EN/IEC 62040-2, EN/IEC 62040-3, ISO 14001, ISO 9001, LCIE
Standard warranty
1 year repair or replace

General

Bypass Connection
4 wire (3P + N), 5 wire (3P + N + E)
Bypass Protection Device
800.0
Max Bypass Input Current
844.0A

Options

Services