Why does my Symmetra Power Array 3:1 UPS not show three input phases on the PowerView display?
Issue:
Symmetra Power Array 3:1 UPS does not show three input phases on the PowerView display interface.

Product Line:
Symmetra Power Array

Environment:
3:1 systems only

Cause:
If using a PowerView firmware revision prior to rev N, all three input phases will not be properly reflected.

Resolution:
When using a PowerView on Symmetra Power Array 3:1 you must use a PowerView of firmware revision N or later.

To check the Firmware revision of the PowerView follow these steps:

1. Press any key to go to Menu screen

2. Scroll to Display menu and press enter

3. Scroll down to Information and press enter

4. Firmware is indicated in bottom right corner as FW=N4a (example only)


Schneider Electric South Africa

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.