Can a Motor Driven Load be used with an Easy UPS / Back-UPS?
No, an Easy-UPS or Back-UPS use a step-approximated sine waveform on the output of the UPS to the load. The Easy-UPS and Back-UPS models are intened to be used with computers and peripheral devices. These models are not intended to be used with motor driven equipment. If a motor driven load has been attached to the UPS, it may cause premature damage to the UPS.

Please refer to the below extracted from the user manual under troubleshooting section:


Motor Driven Loads

APC USA

Can a Motor Driven Load be used with an Easy UPS / Back-UPS?
No, an Easy-UPS or Back-UPS use a step-approximated sine waveform on the output of the UPS to the load. The Easy-UPS and Back-UPS models are intened to be used with computers and peripheral devices. These models are not intended to be used with motor driven equipment. If a motor driven load has been attached to the UPS, it may cause premature damage to the UPS.

Please refer to the below extracted from the user manual under troubleshooting section:


Motor Driven Loads

APC USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.