{}

Our Brands

Search FAQs

Galaxy 5000, Galaxy 5500; Dust Covers



Issue:
It has been determined that dust and other foreign conductive particles have been getting inside the UPS during shipping or from site construction projects during installation.

Product line:
Galaxy 5000, Galaxy 5500

Environment:
All models, all serial numbers

Cause:
Conductive dust and particles negatively affect system operation by increasing component temperatures and reducing dielectric strength.



Resolution:
Temporary front and top covers are being applied to Galaxy 5000 units prior to shipping to protect the unit from foreign particles.



FRONT dust protection cover



TOP dust protection cover
Only Schneider Electric Certified Field Service Engineers are authorized to remove this cover.

Bottom Portion can be lifted to provide access to input / output wiring section.




APC USA

Explore more
Range:
Galaxy 3500MGE Galaxy 4000EPS 7000EPS 8000Galaxy 5000
Explore more
Range:
Galaxy 3500MGE Galaxy 4000EPS 7000EPS 8000Galaxy 5000
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.