undefined undefined
{}

Our Brands

Search FAQs
APC KVM Switches and Corresponding Cables/Server Modules

APC KVM Part Numbers and Corresponding Cables/Server Modules


KVMXXXX Series KVM Switches/Cabling

The KVMXXXX series of KVM Switches include KVM0108A, KVM0116A, KVM1116P, KVM0216A, KVM2116P, and KVM2132P. There is no backwards or forwards compatibility between this series and any other KVM models or families listed below except for the AP5641 power management cables and AP5262/AP5262 daisy chain cables as listed below.

KVM0108A/KVM0116A - SMB Analog KVMs are compatible with:
  • KVM-USB - APC KVM 2G, Server Module, USB
  • KVM-PS2 - APC KVM 2G, Server Module, PS/2
  • AP5262 - APC KVM Daisy-Chain Cable - 2 ft (0.6 m)
  • AP5263 - APC KVM Daisy-Chain Cable - 6 ft (1.8 m)
    • Please note: It is possible to connect AP5262/AP5263 together for a maximum length of 18 ft.

KVM1116P, KVM2116P, KVM2132P - SMB/Digital IP KVMs are compatible with:
  • KVM-USB - APC KVM 2G, Server Module, USB
  • KVM-PS2 - APC KVM 2G, Server Module, PS/2
  • KVM-USBVM - APC KVM 2G, Server Module, USB with Virtual Media
  • KVM-PS2VM - APC KVM 2G, Server Module, PS/2 with Virtual Media
  • KVM-USBVMCAC - APC KVM 2G, Server Module, USB with Virtual Media and CAC
  • KVM-SERIAL - APC KVM 2G, Server Module, Serial
  • AP5641 - APC KVM Power Management Cable


The analog KVM (AP5602) and Digital IP KVMs (AP5610, AP5615, AP5616) use their own set of server modules and cabling. There is no backward or forward compatibility between the AP56XX KVMs and APC's first generation IP/Cat5 KVM offering (AP54XX). There is also no compatibility between the aforementioned models and the KVMXXXX KVM series, except for the AP5641 power management cable. All require CAT5 or 6 UTP cabling.

AP5602 - CAT5 analog KVM is compatible with:
  • AP5630 APC KVM PS/2 Server Module
  • AP5631 APC KVM USB Server Module
  • AP5632 APC KVM SUN Server Module
AP5610, AP5615, AP5616 - IP KVM's are compatible with
  • AP5630 - APC KVM PS/2 Server Module
  • AP5631 - APC KVM USB Server Module
  • AP5632 - APC KVM SUN Server Module
  • AP5634 - APC KVM USB VM Server Module
  • AP5635 - APC KVM PS/2 VM Server Module
  • AP5636 - APC KVM VT100 Serial Server Module
    • AP5640 - Power supply for Serial Server Module *
  • AP5641 - APC KVM Power Management Cable**

* Power supply for Serial Server Module can support up to (4) APC KVM Serial Server Modules.

** AP5641 is the only supported cable for Power management. AP9317 has similar connections but should NOT be used as it is for a different purpose.


The first generation of APC CAT5 Analog KVM (AP5401) and IP KVM (AP5405) require both a server module and CAT5 or 6 UTP cabling.

AP5401 - 16 port Analog CAT5 KVM (PC PS/2, PC & SUN USB, SUN Mini-DIN)
AP5405 - 16 port IP KVM (PC PS/2, PC & SUN USB, SUN Mini-DIN)

  • AP5460 - CAT5/IP KVM PS/2 Server Module (SM)
  • AP5461 - CAT5/IP KVM USB Server Module (SM)
  • AP5462 - CAT5/IP KVM SUN Server Module (SM)

The APC Multi-Platform Analog KVM Switches with pre-set lengths of cables listed below:

AP5201 - 8 port Multi-Platform Analog KVM (PC PS/2, USB, SUN 13W3 or VGA)
AP5202 - 16 port Multi-Platform Analog KVM (PC PS/2, USB, SUN 13W3 or VGA)
AP5808 - 17" Rack LCD Console with Integrated 8 Port Analog KVM Switch
AP5816 - 17" Rack LCD Console with Integrated 16 Port Analog KVM Switch

  • AP5264 – 3' PS/2 Cable
  • AP5250 – 6' PS/2 Cable
  • AP5251 - 6' SUN (13W3) Cable
  • AP5252 - 6' SUN (VGA) Cable
  • AP5253 – 6' USB Cable
  • AP5254 – 12' PS/2 Cable
  • AP5255 - 12' SUN (13W3) Cable
  • AP5256 - 12’ SUN (VGA) Cable
  • AP5257 – 12’ USB Cable
  • AP5258 - 25' PS/2 Cable
  • AP5259 - 25' SUN (13W3) Cable
  • AP5260 - 25' SUN (VGA) Cable
  • AP5261 - 25' USB Cable
  • AP5262 - 2' AP52XX/AP58XX Daisy Chain Cable
  • AP5263 - 6' AP52XX/AP58XX Daisy Chain Cable
  • AP5821 - 6' USB Extension Cable (AP5808/AP5816 only)
  • AP5822 - 12' USB Extension Cable (AP5808/AP5816 only)
  • AP5823 - 25' USB Extension Cable (AP5808/AP5816 only)




***Note: These KVM switches and related cables are no longer manufactured or sold by APC.

AP9254 4 port KVM (PC only)

  • AP9850 - 10’ PS/2 Cable
  • AP9851 - 25’ PS/2 Cable for AP9254/ AP9258

AP9258 8 port KVM (PC only)
  • AP9850 - 10’ PS/2 Cable for AP9254/ AP9258
  • AP9851 - 25’ PS/2 Cable for AP9254/ AP9258

AP9278 8 port KVM (PC/Sun PS/2, USB)
  • AP9850 - 10’ PS/2 Cable for AP9254/ AP9258
  • AP9851 - 25’ PS/2 Cable for AP9254/ AP9258
  • AP9853 - 15’ Cable for Sun for AP9278
  • AP9854 - 15’ 13W3 Cable for Sun for AP9278
  • AP9855 - 12’ USB Cable for AP9278


Pairing Cable for AP9258 and AP9254 ONLY: AP9852


*NOTE: In order to pair the above KVMs, the units must have a serial number greater than: RA0235


MasterView KVM Part #s and Corresponding Cables


58066 – 4 port KVM (PC only) Cascade up to 64 PCs

  • 58PS2V-Length – Available in 6, 10, 15 and 25 foot lengths, for PS/2 Kbd/Mouse, Video
  • 58ATV-Length – Available in 6, 10, 15 and 25 foot lengths for, PC Kbd, Serial Mouse, Video

58065 – 8 port KVM (PC only) Cascade up to 302 PCs
  • 42011-10 – 10’ Cable for PS/2 Keyboard & Mouse, Video
  • 42010-10 – 10’ Cable for PC Keyboard, Serial Mouse, Video
  • 42014-10 – 10’ Extension cable for 42011 & 42010
  • 58012-3/10 – 3’ or 10’ Cascading cable for 58065 KVM Switch


58068 - 16 port KVM (PC only) Cascade up to 302 PCs, w/ audio

  • 42011-10 – 10’ Cable for PS/2 Keyboard & Mouse, Video
  • 42010-10 – 10’ Cable for PC Keyboard, Serial Mouse, Video
  • 42014-10 – 10’ Extension cable for 42011 & 42010
  • Or 42087-6/10/15 for Audio support as well as PS/2 Kbd/Mouse, Video
  • 42088-2 cascade cable for 58068 KVM Switch


58098 – 4 port KVM (PC only)

  • 58PS2V-Length – 6,10,15 and 25 foot length


58100 – 4 port USB KVM (PC only)

  • 58USB-6 -Length – 6 foot
  • 58USB-10 -Length – 10 foot

APC USA

APC KVM Switches and Corresponding Cables/Server Modules
 

APC KVM Part Numbers and Corresponding Cables/Server Modules


KVMXXXX Series KVM Switches/Cabling

The KVMXXXX series of KVM Switches include KVM0108A, KVM0116A, KVM1116P, KVM0216A, KVM2116P, and KVM2132P. There is no backwards or forwards compatibility between this series and any other KVM models or families listed below except for the AP5641 power management cables and AP5262/AP5262 daisy chain cables as listed below.

KVM0108A/KVM0116A - SMB Analog KVMs are compatible with:
 
  • KVM-USB - APC KVM 2G, Server Module, USB
  • KVM-PS2 - APC KVM 2G, Server Module, PS/2
  • AP5262 - APC KVM Daisy-Chain Cable - 2 ft (0.6 m)
  • AP5263 - APC KVM Daisy-Chain Cable - 6 ft (1.8 m)
    • Please note: It is possible to connect AP5262/AP5263 together for a maximum length of 18 ft.

KVM1116P, KVM2116P, KVM2132P - SMB/Digital IP KVMs are compatible with:
 
  • KVM-USB - APC KVM 2G, Server Module, USB
  • KVM-PS2 - APC KVM 2G, Server Module, PS/2
  • KVM-USBVM - APC KVM 2G, Server Module, USB with Virtual Media
  • KVM-PS2VM - APC KVM 2G, Server Module, PS/2 with Virtual Media
  • KVM-USBVMCAC - APC KVM 2G, Server Module, USB with Virtual Media and CAC
  • KVM-SERIAL - APC KVM 2G, Server Module, Serial
  • AP5641 - APC KVM Power Management Cable

 


 

The analog KVM (AP5602) and Digital IP KVMs (AP5610, AP5615, AP5616) use their own set of server modules and cabling. There is no backward or forward compatibility between the AP56XX KVMs and APC's first generation IP/Cat5 KVM offering (AP54XX). There is also no compatibility between the aforementioned models and the KVMXXXX KVM series, except for the AP5641 power management cable. All require CAT5 or 6 UTP cabling.
 

AP5602 - CAT5 analog KVM is compatible with:
 
  • AP5630 APC KVM PS/2 Server Module
  • AP5631 APC KVM USB Server Module
  • AP5632 APC KVM SUN Server Module
AP5610, AP5615, AP5616 - IP KVM's are compatible with
  • AP5630 - APC KVM PS/2 Server Module
  • AP5631 - APC KVM USB Server Module
  • AP5632 - APC KVM SUN Server Module
  • AP5634 - APC KVM USB VM Server Module
  • AP5635 - APC KVM PS/2 VM Server Module
  • AP5636 - APC KVM VT100 Serial Server Module
    • AP5640 - Power supply for Serial Server Module *
  • AP5641 - APC KVM Power Management Cable**

* Power supply for Serial Server Module can support up to (4) APC KVM Serial Server Modules.

** AP5641 is the only supported cable for Power management. AP9317 has similar connections but should NOT be used as it is for a different purpose.


The first generation of APC CAT5 Analog KVM (AP5401) and IP KVM (AP5405) require both a server module and CAT5 or 6 UTP cabling.

AP5401 - 16 port Analog CAT5 KVM (PC PS/2, PC & SUN USB, SUN Mini-DIN)
AP5405 - 16 port IP KVM (PC PS/2, PC & SUN USB, SUN Mini-DIN)

  • AP5460 - CAT5/IP KVM PS/2 Server Module (SM)
  • AP5461 - CAT5/IP KVM USB Server Module (SM)
  • AP5462 - CAT5/IP KVM SUN Server Module (SM)
     

The APC Multi-Platform Analog KVM Switches with pre-set lengths of cables listed below:

AP5201 - 8 port Multi-Platform Analog KVM (PC PS/2, USB, SUN 13W3 or VGA)
AP5202 - 16 port Multi-Platform Analog KVM (PC PS/2, USB, SUN 13W3 or VGA)
AP5808 - 17" Rack LCD Console with Integrated 8 Port Analog KVM Switch
AP5816 - 17" Rack LCD Console with Integrated 16 Port Analog KVM Switch

  • AP5264 – 3' PS/2 Cable
  • AP5250 – 6' PS/2 Cable
  • AP5251 - 6' SUN (13W3) Cable
  • AP5252 - 6' SUN (VGA) Cable
  • AP5253 – 6' USB Cable
  • AP5254 – 12' PS/2 Cable
  • AP5255 - 12' SUN (13W3) Cable
  • AP5256 - 12’ SUN (VGA) Cable
  • AP5257 – 12’ USB Cable
  • AP5258 - 25' PS/2 Cable
  • AP5259 - 25' SUN (13W3) Cable
  • AP5260 - 25' SUN (VGA) Cable
  • AP5261 - 25' USB Cable
  • AP5262 - 2' AP52XX/AP58XX Daisy Chain Cable
  • AP5263 - 6' AP52XX/AP58XX Daisy Chain Cable
  • AP5821 - 6' USB Extension Cable (AP5808/AP5816 only)
  • AP5822 - 12' USB Extension Cable (AP5808/AP5816 only)
  • AP5823 - 25' USB Extension Cable (AP5808/AP5816 only)

 




***Note: These KVM switches and related cables are no longer manufactured or sold by APC.

AP9254 4 port KVM (PC only)

  • AP9850 - 10’ PS/2 Cable
  • AP9851 - 25’ PS/2 Cable for AP9254/ AP9258

AP9258 8 port KVM (PC only)
  • AP9850 - 10’ PS/2 Cable for AP9254/ AP9258
  • AP9851 - 25’ PS/2 Cable for AP9254/ AP9258

AP9278 8 port KVM (PC/Sun PS/2, USB)
  • AP9850 - 10’ PS/2 Cable for AP9254/ AP9258
  • AP9851 - 25’ PS/2 Cable for AP9254/ AP9258
  • AP9853 - 15’ Cable for Sun for AP9278 
  • AP9854 - 15’ 13W3 Cable for Sun for AP9278
  • AP9855 - 12’ USB Cable for AP9278


Pairing Cable for AP9258 and AP9254 ONLY: AP9852


*NOTE: In order to pair the above KVMs, the units must have a serial number greater than: RA0235
 


MasterView KVM Part #s and Corresponding Cables


58066 – 4 port KVM (PC only) Cascade up to 64 PCs

  • 58PS2V-Length – Available in 6, 10, 15 and 25 foot lengths, for PS/2 Kbd/Mouse, Video
  • 58ATV-Length – Available in 6, 10, 15 and 25 foot lengths for, PC Kbd, Serial Mouse, Video

58065 – 8 port KVM (PC only) Cascade up to 302 PCs
  • 42011-10 – 10’ Cable for PS/2 Keyboard & Mouse, Video
  • 42010-10 – 10’ Cable for PC Keyboard, Serial Mouse, Video
  • 42014-10 – 10’ Extension cable for 42011 & 42010
  • 58012-3/10 – 3’ or 10’ Cascading cable for 58065 KVM Switch


58068 - 16 port KVM (PC only) Cascade up to 302 PCs, w/ audio

  • 42011-10 – 10’ Cable for PS/2 Keyboard & Mouse, Video
  • 42010-10 – 10’ Cable for PC Keyboard, Serial Mouse, Video
  • 42014-10 – 10’ Extension cable for 42011 & 42010
  • Or 42087-6/10/15 for Audio support as well as PS/2 Kbd/Mouse, Video
  • 42088-2 cascade cable for 58068 KVM Switch


58098 – 4 port KVM (PC only)

  • 58PS2V-Length – 6,10,15 and 25 foot length


58100 – 4 port USB KVM (PC only)

  • 58USB-6 -Length – 6 foot
  • 58USB-10 -Length – 10 foot
 

APC USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.