Issue:
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.
Released for:Schneider Electric Egypt and North East Africa
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.
Released for:Schneider Electric Egypt and North East Africa