What is the purpose of the external grounding of an APC Rack PDU or ATS?

Question:
What is the purpose of the external grounding of an APC Rack PDU or ATS?

Product:
APC Rack Power Distribution Units and Rack Automatic Transfer Switches


Environment:
APC Rack Power Distribution Units and Rack Automatic Transfer Switches

Solution:

APC by Schneider Electric rack power distribution units (PDU) and rack automatic transfer switches (ATS) will have an external grounding provision.
PDU grounding.PNG

Please note that high leakage current from attached loads is possible. Please contact the manufacturer of the equipment attached to know the equivalent total leakage current of all your devices. If total leakage current of all attached load exceeds 3.5mA, it is highly advised to attach a ground wire from the Rack PDU or Rack ATS supplementary ground (M5 thread labelled with the ⏚ symbol) to a reliable ground in your facility. This should be done before energizing the Rack PDU or the Rack ATS and installation for this external grounding must be done by a qualified personnel / electrician.
Snip from Safety Information.PNG

Additionally, you may refer to the attached safety documents for our Rack PDU and Rack ATS or you may contact our Tech Support team at 800-800-4272 or chat with us at APC by Schneider Electric for more information.

Schneider Electric Česká republika

Přílohy
Rack PDU Safety Information ML_990-3433H.pdf [1.89 MB]
990-9713G_ML.pdf [1.76 MB]
What is the purpose of the external grounding of an APC Rack PDU or ATS?

Question:
What is the purpose of the external grounding of an APC Rack PDU or ATS?

Product:
APC Rack Power Distribution Units and Rack Automatic Transfer Switches


Environment:
APC Rack Power Distribution Units and Rack Automatic Transfer Switches

Solution:
 

APC by Schneider Electric rack power distribution units (PDU) and rack automatic transfer switches (ATS) will have an external grounding provision.
 
PDU grounding.PNG

Please note that high leakage current from attached loads is possible. Please contact the manufacturer of the equipment attached to know the equivalent total leakage current of all your devices. If total leakage current of all attached load exceeds 3.5mA, it is highly advised to attach a ground wire from the Rack PDU or Rack ATS supplementary ground (M5 thread labelled with the ⏚ symbol) to a reliable ground in your facility. This should be done before energizing the Rack PDU or the Rack ATS and installation for this external grounding must be done by a qualified personnel / electrician.
Snip from Safety Information.PNG

Additionally, you may refer to the attached safety documents for our Rack PDU and Rack ATS or you may contact our Tech Support team at 800-800-4272 or chat with us at APC by Schneider Electric for more information.

 
 

Schneider Electric Česká republika

Přílohy
Rack PDU Safety Information ML_990-3433H.pdf [1.89 MB]
990-9713G_ML.pdf [1.76 MB]
Zjistěte více
Kategorie:
Zjistěte více
Kategorie:
Zjistěte více
Kategorie:
Zjistěte více
Kategorie:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.