Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Jak vám dnes můžeme pomoci?
How do I update the firmware of my SRC series Smart-UPS?
Issue: There are two methods to update the firmware of Smart-UPS SRC models:
  • locally, via Serial connection only using the Firmware Upgrade Wizard v4.3.1.1_SRC application
  • remotely via the Network Management Card (NMC)
Note: The download link for the Chinese translation of this FAQ article is available at the end of this document..

If a previous version of the Firmware Upgrade Wizard or Firmware Images are installed, delete the old version and download the version attached to this article.

The download links for the necessary files can be found at the end of this document.

Product Line: SRC5KUXI, SRCE6KUXI, SRC6KUXICH, SRC10KUXI, SRC10KUXICH

Environment:

The system requirements for the Firmware Upgrade Wizard v4.3.1.1_SRC are as follows:
Operating systems: 64-bit Microsoft Windows 7, Windows 2016, Windows 8.1, Windows 10

To find the current UPS Firmware version via the UPS LCD display:
The Firmware Upgrade Wizard will detect the current version.
Alternately, from the main menu of the UPS LCD screen, select "About" and scroll down to "UPS Firmware".

To find the current UPS Firmware version via Firmware Upgrade Wizard:
Run the Firmware Upgrade Wizard and it will identify the current firmware version before performing the update.

To find the current UPS ID:
Every Smart-UPS has a unique UPS ID. This can be found in the "About" menu on the UPS LCD screen, or in the NMC web interface.
  • Follow the link the video guide on How to locate the UPS ID for APC Smart-UPS
  • The same models of UPS may have different UPS IDs depending on when they were produced.
  • The final firmware version will be determined by the UPS ID and not the Model Number of the UPS.
  • If the UPS ID is not listed in the below table, it does not have an update available.
  • The Firmware Upgrade Wizard will select the correct version for the unit you are updating.
Note: it is not recommended to perform a firmware downgrade to a lower firmware version than the current UPS firmware.
UPS IDUPS ModelLatest Firmware FileFirmware Version After Update
1006SRC5KUXISRC5KUXI_ID_1006_UPS_14-0.encUPS 14.0
1006SRCE6KUXISRCE6KUXI_ID_1006_UPS_14-1.encUPS 14.1
1006SRC6KUXICHSRC6KUXICH_ID_1006_UPS_14-2.encUPS 14.2
1011SRC10KUXISRC10KUXI_ID_1011_UPS_14-0.encUPS 14.0
1011SRC10KUXICHSRC10KUXICH_ID_1011_UPS_14-1.encUPS 14.1


Resolution:

UPS Firmware Update Instructions

IMPORTANT:
  • The UPS output must be turned off before the UPS firmware update
  • The UPS must be connected to AC input
  • The UPS battery must remain connected during the UPS firmware update
  • The serial cable, part number 940-8311 or 940-1525, supplied with the UPS must be used
Verify the hash key of the Firmware Upgrade Wizard after downloading. The current hash value is c0dee62920c76e617f746a628bc1b0a6.
  1. Open Command Prompt.
  2. Change the directory to the folder where the downloaded Smart-UPS_Firmware_Upgrade_Wizard_v4.3.1.1_SRC.exe was saved:
    • This is typically done using the "cd" command
    • For example, if the Smart-UPS_Firmware_Upgrade_Wizard_v4.3.1.1_SRC.exe file was saved to the Downloads folder, the command may look like: "cd C:\Users\Username\Downloads", or "cd Downloads"
  3. Run the command "certutil -hashfile Smart-UPS_Firmware_Upgrade_Wizard_v4.3.1.1_SRC.exe MD5"
  4. Compare and verify that the displayed hash value corresponds to c0dee62920c76e617f746a628bc1b0a6.
Example:

hash

UPS Firmware Update using the Firmware Upgrade Wizard:

Step 1A
:
  • Turn off the UPS output, and connect the DB-9 to RJ45 cable part number: 940-8311 or 940-1525,  between the UPS and the computer used to update the UPS firmware.
  • Download and unzip Smart-UPS_Firmware_Upgrade_Wizard_v4.3.1.1_SRC.exe
  • Identify and download the applicable UPS firmware file for the UPS model you are updating from the above table. Save the files on a local drive.
Step 2A:
  • Double click the extracted FirmwareUpgradeWizard.exe
  • Ensure that the Firmware Upgrade Wizard version shown is 4.3.1.1.80643 and select "Next":
FUW2A

Step 3A:
  • Select "Next" after checking the "I agree to terms in the License Agreement" checkbox:
FUW3A

Step 4A:
  • Choose the computer's communication port the UPS communication cable is connected to, and select "Next":
FUW4A

Step 5A:
  • The Wizard will check for UPS compatibility.
  • Select "Next" once compatibility has been confirmed:
FUW5A1
FUW5A2

Step 6A
  • Select "Browse", then select the UPS firmware file:
  • Note: refer to the above table to identify the correct UPS firmware file
FUW6A

Step 7A:
  • Select "Next":
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.