{}

Our Brands

Search FAQs

Video: How to place Galaxy VM UPS into Maintenance Bypass

Issue:
How to place Galaxy VM UPS into Maintenance Bypass

Product line:
Galaxy VM

Environment:
All Product models, all serial numbers

Cause:
The UPS must be transitioned into maintenance bypass mode for certain types of service or other maintenance to the system.

Resolution:
Push the Home screen Icon
Push CONTROL, default password 1234
Select SHUTDOWN WIZARD
Select Shutdown ending in Maintenance Bypass, now follow the on screen instructions

This video provides a step by step instruction on how to transition the Galaxy VM UPS into Maintenance Bypass mode, allowing the end-user to power down the UPS without interruption to their load.



Also see article FA243122 to take unit out of Maintenance Bypass

APC Belgium

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.